MMC PAKISTAN �� SmoothAir – Row Mount Precision Cooling

Smooth Air – Row Mount Precision Cooling

Row mounting and airflow front/side discharge design bring cooling closer to the heat source, with intelligent controls that dynamically regulate output for improved cooling efficiency.

TALK TO MMC

Plan your next step with our team

Share your requirements, location and timeline. We��ll help you define a suitable solution and delivery scope.

[email protected]
Talk to our team

SmoothAir Row Mount enquiry. We reply within one business day.

Or call +92 311 1555053

5.6 – 90.1 kWAir / water cooled
28.9 – 65.8 kWChilled water
PUE 1.2Indirect free cooling
-40℃ – 55℃Continuous working
Row Cooling System

Row Cooling System

Multiple configuration with air-cooled, water-cooled, and chilled water types, high reliability with world leading brand components support -40°C – 55°C continuous working. Full range of models are available to meet the needs of today's IT environments.

Suited for
Finance & BankingEducationMedicalGovernmentEnterpriseTelecom

Sustainable Energy Efficiency

  • Top components from leading brands and unique design assure high reliability of products.
  • Available in multi size and seamlessly fitting into the IT rack system, you can make the most of your valuable real estate while ensuring efficient cooling.
  • Inverter compressor and EC fan with intelligent control system ensure precise temperature control.
  • Indirect Free Cooling with Refrigerant Pump Technology for minimizing the energy consumption of the in-row cooling system.
Sustainable Energy Efficiency

Green Efficiency Free Cool

  • Indirect free cooling with refrigerant pump technology, PUE low to 1.2.
  • No water consumption during free cooling mode.
  • No water loop introduced into server room, no flooding concern.
  • Indirect type No dust, moisture concern.
  • Automatic mode switching, and no complex maintenance and service.
Green Efficiency Free Cool

Intelligent Control System

  • Industry leading smart control system, with insightful sensor data and intelligent control logics.
  • All digital control to major components, maintaining optimum working status, and flexible adjustment per onsite working conditions.
  • 1000+ alarm records, and 7days history pressure curve records, 7days history temperature curve records.
  • Smart monitoring protocols: Web/SNMP/Modbus/Bac-net/Email/Dry contact/IPV6.
  • Teamwork function including Master/Slave Working mode, Master Control mode and Force Working mode.
  • Built in web server support visit with web-browser from computers and mobile devices, can view, control unit through web.
Intelligent Control System

Highly Customized Options

Available in three widths and three depths, air flow front / side discharge, and adjustable vent air baffle. Allows us to provide a customized fit for different data center configurations. Suitable for racks from any manufacturers, you can also easily expand or reconfigure your existing infrastructure without disrupting the existing setup.

Highly Customized Options

All Types of Cooling System

Air Cooled Split

Air Cooled Split

5.6-90.1kW · 300/600/900 Width
  1. Air cooled, row mount, split type, ideal for micro data center, integrated modular data center solutions.
  2. Dynamically modulated cooling capacity with inverter compressor maintains temperature within envelop and prevent compressor from cycling during low heat load period.
  3. Air flow modulates with EC fans to match IT requirements. Each fan module is easy to change with quick couple connections.
  4. Precision cooling controller monitors and protects unit constantly. Easy to be integrated into BMS to display, control and manage the system.
  5. R410A green refrigerant is highly efficient and no ODP. Optional R134A refrigerant for high ambient site up to 55C.
  6. Copper/water piping support bottom and top connections.
  7. Airflow direction is configurable upon order for easier integration with different types of data center layout.
Request pricing →
Air Cooled Packaged

Air Cooled Packaged

5.6-10.8kW · 300mm Width
  1. Air cooled package type cooling unit, ideal for data center without space for outdoor condenser.
  2. Dynamically modulated cooling capacity with inverter compressor maintains temperature within envelop and prevent compressor from cycling during low heat load period.
  3. Air flow modulates with EC fans to match IT requirement requirements. Each fan module is easy to change with quick couple connections.
  4. Precision cooling controller monitors and protects unit constantly. Easy to be integrated into BMS to display, control and manage the system.
  5. Built in condenser with EC fan speed adjustable to meet tight space application. Optional with duct hose to be connecting to air vent.
  6. Easy to touch electric box makes service convenient.
  7. Optional with SNMP communication, condensate pump, water leaking kit.
Request pricing →
Water Cooled

Water Cooled

5.6-90.1kW · 300/600/900 Width
  1. Dynamically modulated cooling capacity with inverter compressor maintains temperature within envelop and prevent compressor from cycling during low heat load period.
  2. Air flow modulates with EC fans to match IT requirements. Each fan module is easy to change with quick couple connections.
  3. Precision cooling controller monitors and protects unit constantly. Easy to be integrated into BMS to display, control and manage the system.
  4. Touch type color display panel to easily view and control the units.
  5. Copper piping adopts quick connection and supports bottom and top connections.
  6. Easy to change G4 air filter and sealed doors help to build a clean and quiet MDC.
Request pricing →
Chilled Water Cooled

Chilled Water Cooled

28.9-65.8kW · 300/600mm Width
  1. Chilled water, row mount, ideal for modular data center and container data center solutions.
  2. Dynamically modulated cooling capacity with inverter compressor maintains temperature within envelop and prevent water flow from cycling during low heat load period.
  3. Air flow modulates with EC fans to match IT requirement requirements. Each fan module is easy to change with quick couple connections.
  4. Precision cooling controller monitors and protects unit constantly. Easy to be integrated into BMS to display, control and manage the system.
  5. Touch type color display panel to easily view and control the units.
  6. Copper piping adopts quick connection and supports bottom and top connections.
  7. Easy to change G4 air filter and sealed doors help to build a clean and quiet MDC.
Request pricing →

Key Components

Inverter Compressor

Inverter Compressor

  • Stable temperature control per heating load by adjusting compressor output.
  • Reducing energy cost and improve compressor working life.
  • Green refrigerant R410A no ODP effect.
  • Capacity adjustable 30%-100%.
EC Fans

EC Fans

  • Best in class design and reliability.
  • Highest efficiency EC Fan system.
  • Speed adjustable 0%-100%.
  • Direct drive system no belts easier replacement and service.
  • Higher external static flexible for special application.
Electronic Expansion Valve

Electronic Expansion Valve

  • Automatically modulating refrigerant flow per system requirement.
  • Better COP performance during low temperature season comparing TEV system.
  • Better refrigerant flow feeding during compressor startup, to reach higher reliability of compressor working.

Technical data

Technical data from the ATTOM product brochure.

Row Mount Split DX

ModelS-005RAS-007RAS-012RAS-017RAS-020RAS-025RAS-030RAS-040RAS-050RAS-065RAS-075RAS-090RA
Total cooling (kW)5.67.612.817.621.225.131.140.951.265.776.890.1
Air volume (m³/h)2000225024004500492050005800800010000120001350016000
Height (mm)200020002000200020002000200020002000200020002000
Depth (mm)110011001100110011001100110011001100110011001100
Width (mm)300300300300300300300600600600900900
Weight (kg)210213233253258260320360420460540620
Reheat (kW)3.03.03.06.06.06.06.06.06.06.06.06.0
Humidifier, optional (kg/h)1.51.51.51.51.51.5333333
Standard outdoor unitKSF08ANKSF12ANKSF18ANKSF24ANKSF32ANKSF38ANKSF42ANKSF52ANKSF62ANKSF85ANKSF52ANKSF62AN
Outdoor unit qty111111111122
Power input208-240V/50-60Hz/1Ph-2Ph208-240V/50-60Hz/1Ph-2Ph208-240V/50-60Hz/1Ph-2Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph

Row Mount Package DX

ModelS-005PAS-007PAS-010PA
Total cooling (kW)5.67.610.8
Air volume (m³/h)200022502500
Height (mm)2000(42U)2000(42U)2000(42U)
Depth (mm)120012001200
Width (mm)300300300
Weight (kg)210213233
Reheat (kW)3.03.03.0
Humidifier, optional (kg/h)1.51.51.5
Cooling typeDX Self-ContainedDX Self-ContainedDX Self-Contained
Power input208-240V/50-60Hz/1Ph-2Ph208-240V/50-60Hz/1Ph-2Ph208-240V/50-60Hz/1Ph-2Ph

Row Mount Chilled Water

ModelS-025RCS-045RCS-065RC
Air volume (m³/h)4800900011400
Height (mm)2000(42U)2000(42U)2000(42U)
Depth (mm)110011001100
Width (mm)300600600
Weight (kg)190330400
Reheat (kW)3.03.03.0
Humidifier, optional (kg/h)1.51.51.5
Total capacity, 37℃/24% return air (kW) at 7/12 · 10/15 · 13/18 ℃ water38.8 · 33.0 · 28.959.8 · 52.4 · 46.087.0 · 75.0 · 65.8
Power input208-240V/50-60Hz/1Ph-2Ph380-415V/50-60Hz/3Ph380-415V/50-60Hz/3Ph
Notes
1. Air flow is based upon standard speed setting. Fan modulates per real loads.
2. Cooling Capacity based on 37°C/24°C/50%RH return air and 35°C condensing temperature.

ATTOM data centers at mission-critical sites

Deployments of ATTOM, the data center brand MMC supplies, installs and supports in Pakistan. Case studies published by ATTOM.

AgileMod containment data center for CPPA-G
Energy · Islamabad, Pakistan

AgileMod containment data center for CPPA-G

A dual-row, six-rack cold-aisle containment system with overhead cable trays and multi-factor access control for Pakistan's Central Power Purchasing Agency.

Read ATTOM case study
AgileCub data center for the Central Reserve Bank
Finance · El Salvador

AgileCub data center for the Central Reserve Bank

A high-security container data center with bullet-resistant protection, access control and redundant power, delivered on a shorter timeline with efficient cooling.

Read ATTOM case study
Tier III container data center for Mindanao State University
Education · Philippines

Tier III container data center for Mindanao State University

A containerised data center with redundant power, precision cooling and real-time monitoring, part of MSU's move to a smart campus.

Read ATTOM case study

RESOURCES

Planning in-row cooling for your data center?

Talk to our cooling experts to choose the right capacity and configuration for your site.

Planning in-row cooling for your data center?

Get SmoothAir Row Mount from MMC

Tell us about your site and load. We will recommend the right configuration and send a detailed quote.

  • Authorised ATTOM partnerGenuine ATTOM products and warranty, supplied locally.
  • Site survey & designOur engineers size the cooling capacity for your heat load and space.
  • Installation & commissioningDelivery, installation and commissioning by MMC’s data center team.
  • Ongoing supportMaintenance and support from our Karachi head office.
Talk to our team

SmoothAir Row Mount enquiry. We reply within one business day.

Or call +92 311 1555053

Plan with MMC

In row cooling design

In row cooling places cooling capacity near the racks generating heat. Assess SmoothAir Row Mount against rack density, containment and the arrangement of supply and return air.

Define the requirement

Share the rack row layout, per-rack loads and hot/cold aisle arrangement. Include piping or refrigerant routes and outdoor plant constraints where relevant.

Compare the delivery scope

Evaluate resilience, access and controls across the whole row. Confirm the operating conditions and commissioning tests in the technical proposal.

Our reach

Countries we serve

  • Pakistan flagPakistan
  • USA flagUSA
  • Australia flagAustralia
  • Belgium flagBelgium
  • Paraguay flagParaguay
  • Denmark flagDenmark
  • UK flagUK
  • Afghanistan flagAfghanistan
  • Philippines flagPhilippines
  • Turkey flagTurkey
  • Thailand flagThailand
  • Canada flagCanada
  • Sweden flagSweden
  • Singapore flagSingapore
  • Colombia flagColombia
  • UAE flagUAE
  • New Zealand flagNew Zealand
  • Kyrgyzstan flagKyrgyzstan
  • France flagFrance
  • Switzerland flagSwitzerland
  • Tanzania flagTanzania
  • Uganda flagUganda
  • Tajikistan flagTajikistan
  • China flagChina
  • Italy flagItaly
  • Finland flagFinland
  • Qatar flagQatar
  • Zimbabwe flagZimbabwe
  • Saudi Arabia flagSaudi Arabia